Recall #18-731 · Published March 19, 2018

Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option

Carrier® Recalls to Repair Commercial Rooftop HVAC Units Due to Fire Hazard (Recall Alert)

CPSC published a recall notice for Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option from Carrier México, S.A. de C.V. on March 19, 2018. CPSC identifies this hazard: The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard. The official remedy states: Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.

40/50 series LC rooftop HVAC unit
40/50 series LC rooftop HVAC unit
Image: CPSC recall notice

What to check on the product label

Compare every letter, number, space, and suffix. A similar-looking product may not be included in this recall.

Affected model numbers

48/50LC07-2614TH48LCTA24F2M5-0S1B3
Additional identifying details

The model numbers are 48/50LC07-26 with an A in the 6th digit and a 0 (zero) in the 14th digit of the model number (e.g., 48LCTA24F2M5-0S1B3).

Why it was recalled

The HVAC's humidimizer fan can fail to shut off when a connected smoke detector is tripped, posing a fire hazard.

Incidents and injuries

Carrier has received one report of a fan not shutting off during installation testing. No injuries have been reported.

Official remedy

Purchasers should immediately contact their Carrier dealer for a free repair, which consists of free replacement and installation of the electronic control board. The firm is contacting all known purchasers.

Remedy type: Repair

Product and sales details

Manufacturer
Carrier México, S.A. de C.V.
Recall number
18-731
Units
About 530
Manufactured in
Mexico
Sold at / sales period
Carrier distributors nationwide from March 2014 to September 2017 for between $25,000 and $93,000.
Importer
Carrier Corporation, of Jupiter, Fla.

Carrier WeatherExpert commercial packaged rooftop HVAC units with humidimizer option

Recall contact information

Carrier toll-free at 844-864-8748 from 8 a.m. to 5 p.m. ET Monday through Friday, or online at www.carrier.com and click on “Product Safety Recall” to locate a local Carrier dealer for more information.

Verify phone numbers, hours, and websites on the current CPSC notice before contacting the firm.

Publication and verification

  1. Recall published

  2. Home Recall Watch last verified

    From the verified CPSC data snapshot this site is built from.