Recall #04-229 · Published September 30, 2004

Package Terminal Air Conditioner/Heat Pump (PTAC)

CPSC, Goodman Company, L.P. Announce Recall of Amana, Trane, and American Standard Brand Package Terminal Air Conditioners/Heat Pumps

CPSC published a recall notice for Package Terminal Air Conditioner/Heat Pump (PTAC) from Package Terminal on September 30, 2004. CPSC identifies this hazard: Fire hazard, resulting from this chain of events: filter becomes clogged due to lack of maintenance, severely restricting airflow and resulting in elevated internal temperature; this may cause two safety switches to stop working during the product's expected life; if the blower wheel then stops when the product is operated in the heating mode, a fire hazard can develop. The official remedy states: Free thermal safety limit switch. Commercial and institutional owners will install the replacement switch themselves. Individual homeowners can get a free repair. Contact the Goodman Hotline to receive the free replacement thermal safety switch. Inspect and clean the air conditioner/heat pump filters immediately to remove any imminent hazard. Continue to clean these filters every 30 days in accordance with manufacturer's recommendations, which can be found at www.regcen.com/PTAC.

Recalled Package Terminal Air Conditioner/Heat Pump (PTAC)
Recalled Package Terminal Air Conditioner/Heat Pump (PTAC)
Image: CPSC recall notice

What to check on the product label

Compare every letter, number, space, and suffix. A similar-looking product may not be included in this recall.

Affected model numbers

PTH073A35PTH074A35PTH093A35PTH093A50PTH094A35PTH094A50PTH123A35PTH123A50PTH124A35PTH124A50PTH153A35PTH153A50PTH154A35PTH154A50PTC073A35PTC074A35PTC093A35PTC093A50PTC094A35PTC094A50PTC123A35PTC123A50PTC124A35PTC124A50PTC153A35PTC153A50PTC154A35PTC154A50PTHC0701GPTHC0702GPTHC0901GPTHC0901JPTHC0902GPTHC0902JPTHC1201GPTHC1201JPTHC1202GPTHC1202JPTHC1501GPTHC1501JPTHC1502GPTHC1502JPTEC0701GPTEC0702GPTEC0901GPTEC0901JPTEC0902GPTEC0902JPTEC1201GPTEC1201JPTEC1202GPTEC1202JPTEC1501GPTEC1501JPTEC1502GPTEC1502J
Additional identifying details

Check the product label for these CPSC-listed model numbers: PTH073A35, PTH074A35, PTH093A35, PTH093A50, PTH094A35, PTH094A50, PTH123A35, PTH123A50, PTH124A35, PTH124A50, PTH153A35, PTH153A50, PTH154A35, PTH154A50, PTC073A35, PTC074A35, PTC093A35, PTC093A50, PTC094A35, PTC094A50, PTC123A35, PTC123A50, PTC124A35, PTC124A50, PTC153A35, PTC153A50, PTC154A35, PTC154A50, PTHC0701G, PTHC0702G and 26 more.

Why it was recalled

Fire hazard, resulting from this chain of events: filter becomes clogged due to lack of maintenance, severely restricting airflow and resulting in elevated internal temperature; this may cause two safety switches to stop working during the product's expected life; if the blower wheel then stops when the product is operated in the heating mode, a fire hazard can develop.

Incidents and injuries

Goodman received 29 confirmed reports of units overheating, including eight instances where the PTAC ignited and, in some cases, caused minor property damage. No injuries have been reported.

Official remedy

Free thermal safety limit switch. Commercial and institutional owners will install the replacement switch themselves. Individual homeowners can get a free repair. Contact the Goodman Hotline to receive the free replacement thermal safety switch. Inspect and clean the air conditioner/heat pump filters immediately to remove any imminent hazard. Continue to clean these filters every 30 days in accordance with manufacturer's recommendations, which can be found at www.regcen.com/PTAC.

Product and sales details

Manufacturer
Goodman Company, L.P., of Houston, Texas
Recall number
04-229
Units
About 875,000
Manufactured in
United States
Sold at / sales period
Amana, Trane, and American Standard representatives sold the PTACs to hotels/motels, hospitals, assisted living facilities, schools, and apartment complexes. Heating, ventilation and air conditioning distributors and resellers sold the units to commercial customers and, in some cases, homeowners. The recalled units were sold throughout the U.S. and parts of Canada between January 1996 and March 2003.

Package Terminal Air Conditioner/Heat Pump (PTAC)

CPSC product type: Air Conditioners

Recall contact information

Call the Goodman Hotline at (800) 729-6122 between 7 a.m. and 6 p.m. CT Monday through Friday. Owners can submit a PTAC Recall Information Form at Goodman's website www.regcen.com/PTAC

Verify phone numbers, hours, and websites on the current CPSC notice before contacting the firm.

Publication and verification

  1. Recall published

  2. CPSC record last published

  3. Home Recall Watch last verified

    From the verified CPSC data snapshot this site is built from.

Related recalls

Selected by shared brand or household-product category.