RecalledRecall 03-502Published

Invensys Building Systems Siebe actuators

CPSC, Invensys Building Systems Announce Recall of Siebe Actuators in Building Fire/Smoke Dampers

Hazard
Fire
Units
Up to 560,000 units
Incidents
Incidents reported
Remedy
See the notice

CPSC recall 03-502, announced October 2, 2002, covers Invensys Building Systems Siebe actuators (up to 560,000 units). A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Recall contact: call (877) 481-2372, or go to www.regcen.com/MA200.

What to check on the product label

Compare the model on your label, then check any serial numbers, date codes, and exclusions in the notice. A model match alone does not confirm that your unit is included.

The CPSC data does not provide a discrete model-number list for this record. Compare the product description and identification details on the official notice.

Which products are included?

Actuators hold open fire and smoke dampers in a building's heating, ventilation and air conditioning (HVAC) system. A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. These MA-200 and MA-200-1 series actuators were used in fire and smoke dampers that were manufactured by various companies from December 1993 through October 1999, which were installed by private contractors in commercial and residential buildings. The actuators have manufacture date codes of 9348 through 9947.

Confirm these details on the official CPSC notice

Why it was recalled

A spring mechanism integrated with the damper, is designed to close the damper during a fire to limit the spread of smoke, fire and fumes. The recalled actuators can jam and prevent the dampers from closing. If dampers fail to close during a fire, serious injury or death can be suffered by building occupants because smoke, fire and fumes can spread through a building's ventilation system.

Incidents and injuries

Building owners, damper manufacturers, and fire and safety investigators have reported dampers not closing during testing.

Official remedy

To be eligible for a free actuator replacement, the building owner must test the actuator and report the results to Invensys. Only actuators that fail testing will be replaced.

Product and sales details

Brand
Invensys Building Systems
Recall number
03-502
Units
Up to 560,000
Manufactured in
United States
Sold at / sales period
The actuators were installed by private contractors in commercial and residential buildings.
Distributor
Invensys Building Systems, of Love Park, Ill.

Siebe actuators

CPSC product type: Dampers

Recall contact information

Building owners and managers whose buildings have dampers containing Invensys/Siebe actuators should immediately contact Invensys' Program Coordination Office at (877) 481-2372 between 7 a.m. and 7 p.m. CT Monday through Friday. A web site where building owners can obtain a complete copy of the program information has been established at www.regcen.com/MA200

Verify phone numbers, hours, and websites on the current CPSC notice before contacting the firm.

Know someone who has one?

Recalls only work when owners hear about them. Send this notice to family or friends who might own the same product.

Related recalls

Other notices from the same brand or product category.