Recall #12-721 · Published February 15, 2012

Bosch Security Systems Fire Alarm Control Panel

Fire Control Panels Recalled by Bosch Security Systems Corp. Due to Alarm Failure Posing a Fire Hazard

CPSC published a recall notice for Fire Alarm Control Panel from Bosch Security Systems on February 15, 2012. CPSC identifies this hazard: On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken. The official remedy states: All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

Recalled Bosch fire control panel
Recalled Bosch fire control panel
Image: CPSC recall notice

What to check on the product label

Compare the model on your label, then check any serial numbers, date codes, and exclusions in the notice. A model match alone does not confirm that your unit is included.

Affected model numbers

Additional identifying details

The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen.

Which products are included?

The Bosch-branded fire alarm panel is locking red wall box with dimensions 22.7" high by 14.5" wide by 4.3" deep. The status, date and time can be seen through a glass screen on the panel door. The word "BOSCH" is printed on the right corner of the panel and the model number "FPA-1000-UL" is printed on the bottom left below the glass screen. The alarm panels featured software versions 1.10, 1.11 and 1.12, which can be determined by installers. They were designed to be used in small to medium-sized facilities in both public and residential buildings.

Confirm these details on the official CPSC notice

Why it was recalled

On all systems, when the alarm verification feature of the system is turned on, the control panel can fail to sound an alarm if a fire occurs. In addition, on systems with 50 or more reporting stations, a delay in sounding an alarm and reporting a fire may occur if the loop for the alarm system is broken.

Incidents and injuries

None reported.

Official remedy

All distributors and installers are being sent two technical bulletins. One provides instructions for how to implement a software change that will correct the verification feature. The second contains instructions for how to handle warnings from affected systems with 50 or more stations. Those who have not received the bulletins should contact Bosch.

Remedy type: New Instructions

Product and sales details

Manufacturer
Bosch Security Systems, Inc., of Fairport, N.Y.
Product type
Smoke alarms
Recall number
12-721
Units
About 330
Manufactured in
China
Sold at / sales period
Authorized distributors and installers nationwide from May 2009 through October 2011 for about $1,200.

Fire Alarm Control Panel

CPSC product type: Fire or Smoke Alarms

Recall contact information

For more information, contact Bosch Security Systems at (800) 289-0096 between 8:00 a.m. and 8:00 p.m. ET or visit service/customer care on the firm's website at http://www.boschsecurity.us/en-us/ for instructions on how to download software to update the control panels or otherwise address the problems.

Verify phone numbers, hours, and websites on the current CPSC notice before contacting the firm.

Related recalls

Selected by shared brand or household-product category.

No. 12-701Smoke & CO Alarms

ADT Recalls Carbon Monoxide Detectors Due to Failure to Properly Indicate End of Useful Life

Sensor System

Hazard: When the CO detectors reach the end of their useful life, they should send a signal to make a sound in the home alarm panel alerting consumers it is time to replace them and a signal to ADT's alarm monitoring center. Some of the detectors were not wired properly to the ADT alarm system, resulting in the sound not going off in the home alarm panel and no signal to the ADT alarm monitoring center at the end of its useful life. Not replacing a CO detector at the end its useful life poses a CO poisoning hazard to consumers.

Models