Recall #10-354 · Published September 23, 2010

Siemens and Murray Circuit Breakers, Load Centers and Meter Combos

Siemens Recalls Circuit Breakers Due to Fire Hazard

CPSC published a recall notice for Siemens and Murray Circuit Breakers, Load Centers and Meter Combos from Siemens Industry on September 23, 2010. CPSC identifies this hazard: The recalled circuit breakers have a spring clip that can break during normal use, leading to a loss of force to maintain a proper electrical connection in the panelboard. This can lead to excessive temperature, arcing or thermal damage at the connection point, and damage to the panelboard's electrical insulation and can result in a fire, property damage, or personal injury. The official remedy states: Consumers should immediately contact Siemens for a free inspection by an electrician and a free replacement product.

Circuit Breaker (front view)
Circuit Breaker (front view)
Image: CPSC recall notice

What to check on the product label

Compare the model on your label, then check any serial numbers, date codes, and exclusions in the notice. A model match alone does not confirm that your unit is included.

The CPSC data does not provide a discrete model-number list for this record. Compare the product description and identification details on the official notice.

Additional identifying details

"Siemens" or "Murray," date codes 0610 or 0710 and the catalog number are printed on a label on the side of the circuit breakers.

Which products are included?

This recall involves Siemens and Murray 15 through 50 AMP single and double pole circuit breakers, load centers (circuit breakers that come with an electrical panel), and meter combos (contain a load center and a meter socket). "Siemens" or "Murray," date codes 0610 or 0710 and the catalog number are printed on a label on the side of the circuit breakers. Date codes between June 2010 through August 2010 are stamped on the inside of the metal box of the load centers and meter combos. The catalog number for the load centers and meter combos is printed on a label inside the metal box door and on the packaging. Product Date Codes Catalog Numbers Circuit Breakers 0610, 0710 Q115, Q120, Q130, Q215, Q230, Q250, MP115, MP115U, MP120, MP130, MP215, MP230, MP230U, MP250 Load Centers Jun 23 2010 - Aug 25 2010 G2020B1100CP, G3030B1100CP, G4040B1200CUSGP, LC4040B1200P, G3040B1200CP, G3040L1200CP, G4040B1200CP, G3030B1150CP, W3040B1200CP, G1624L1125CP, W4040B1200CP Meter Combo Jun 23 2010 - Aug 25 2010 JA2040B1200S

Confirm these details on the official CPSC notice

Why it was recalled

The recalled circuit breakers have a spring clip that can break during normal use, leading to a loss of force to maintain a proper electrical connection in the panelboard. This can lead to excessive temperature, arcing or thermal damage at the connection point, and damage to the panelboard's electrical insulation and can result in a fire, property damage, or personal injury.

Incidents and injuries

Siemens has received one report of a circuit breaker spring clip that broke during installation. No injuries have been reported.

Official remedy

Consumers should immediately contact Siemens for a free inspection by an electrician and a free replacement product.

Product and sales details

Recall number
10-354
Units
About 2.2 million
Manufactured in
Mexico
Sold at / sales period
The Home Depot, Lowes, other hardware and building supply stores and numerous electrical distributors nationwide from June 2010 through August 2010 for between $2.50 to $235.
Importer
Siemens Industry Inc., of Alpharetta, Ga.

Siemens and Murray Circuit Breakers, Load Centers and Meter Combos

CPSC product type: Circuit Breakers

Recall contact information

For additional information, contact Siemens at (800) 756-6996 between 9 a.m. and 5 p.m. ET Monday through Friday or visit the firm's website at www.usa.siemens.com