Recall #05-526 · Published December 22, 2004

GE Security Smoke Detector Systems

CPSC, AnnounceGE Security Inc. Retrofit/Recall of Smoke Detector Systems

CPSC published a recall notice for Smoke Detector Systems from GE Security on December 22, 2004. CPSC identifies this hazard: The smoke alarms can fail to activate during a fire or emergency, if installed in combination with certain control panels. The official remedy states: Consumers should contact their system installer or service provider to arrange for a free repair or replacement to make the smoke detectors and control panel systems compatible.

Recalled smoke detector
Recalled smoke detector
Image: CPSC recall notice

What to check on the product label

Compare the model on your label, then check any serial numbers, date codes, and exclusions in the notice. A model match alone does not confirm that your unit is included.

Additional identifying details

Inside the ITI control panel is a label that lists the name and model number of the unit.

Which products are included?

The recalled smoke detection systems involve hard-wired S10A ESL smoke detectors that are incompatible with certain ITI control panels as well as certain S09A/S10A listed ESL smoke detectors that may be incompatible with control panels from other manufacturers. Model numbers are printed on the back of the smoke detectors. Inside the ITI control panel is a label that lists the name and model number of the unit. The following model names and model numbers of ITI control panels are incompatible when installed with the following model numbers of ESL smoke detectors: Smoke Detector Model Numbers 429C 429CT 511C 521B (when SW1 is OFF) 521BXT (when SW1 is OFF) 521NB* 521NBXT* 521NCSXT 711U 711UT 721U 721UT *In addition, the models 521NB and 521NBXT detectors, if installed in the S09A configuration, may self-adjust to an S10A configuration. Thus, these two model detectors may not be compatible with other manufacturer's control panels that are only S09A compatible. ITI Control Panel Model Names and Model Numbers Concord: 60-734-01 60-801 60-801-01 60-792-01-95R-16Z 60-792-01-95R-32Z 60-792-95R-32Z Advent: 60-562 (-01 through -06) Concord Express: 60-806-95R-16Z 60-806-95R

Confirm these details on the official CPSC notice

Why it was recalled

The smoke alarms can fail to activate during a fire or emergency, if installed in combination with certain control panels.

Incidents and injuries

None reported.

Official remedy

Consumers should contact their system installer or service provider to arrange for a free repair or replacement to make the smoke detectors and control panel systems compatible.

Product and sales details

Brand
GE Security
Manufacturer
GE Security Inc., of Austin, Texas
Product type
Smoke alarms
Recall number
05-526
Units
Approximately 246,800 smoke detectors
Manufactured in
United States
Sold at / sales period
Distributors, dealers and installers of security systems nationwide, from June 2002 through October 2004. The smoke detectors and the control panels were sold separately as individual components, and were also sold together as part of a security system for between $180 and $1,150.

Smoke Detector Systems

CPSC product type: Smoke Detectors/Alarms

Recall contact information

Call UTC Fire and Security (formerly GE Security) at 855-286-8889 option 2 between 8am and 8pm ET Monday through Friday.

Verify phone numbers, hours, and websites on the current CPSC notice before contacting the firm.

Related recalls

Selected by shared brand or household-product category.

No. 06-151Smoke & CO Alarms

First Alert® Smoke Alarms and Combination Smoke/CO Alarms Recalled for Rapidly Draining Battery Power

BRK Brands

Hazard: These alarms can drain the power from batteries rapidly, causing premature low battery power. Consumers will be alerted to the low battery power and the need to replace the battery by a chirping of the unit. If the batteries on the smoke/CO alarm are not replaced before the battery power terminates, the alarm will not detect smoke in the event of a possible fire and the presence of carbon monoxide.